Properties
- Thickness: 1-1/2"(38mm)
- Width: 24" (610mm)
- Length: 25' (7620mm)
- Density: 8pcf
- Flame Spread / Smoke Development: less than 25 /
50
- Insulation Melting Point: 2300ºF (1260ºC)
Construction
- Product is a Calcium / Magnesium / Silica for increased
body solubility when compared to ceramic fiber insulation.
- Recommended for use using the same safety guidelines as
fiberglass and mineral wool by the Ontario Construction Safety
Association – 2005 edition.
- Encapsulated in fibre-reinforced foil wrapper to protect
the insulation per NFPA-96 requirements.
Commercial Kitchen Grease Ductwork Testing Standards
- Internal - ULC Grease Duct Testing Protocol
rated for 0" clearance to combustible materials
- External – ISO 6944 Duct “A” Standard
- Tested per NFPA-96 to meet all applicable Canadian Building
Codes as a gypsum shaft alternative
- Listed by Warnock Hersey, a Standards Council of Canada
accredited laboratory
Installation
- Installation Quantity: 2-layers always required
for Commercial Kitchen Grease
- Ductwork applications
- Listed for Butt-Seam Pinning or Banding Installation Methods
|
|
|
|