CL4Fire Code-96™ Grease Duct Insulation System

Listed System: Code-96™


Evaluated by the CCMC as the only fire protection ductwrap product verified to meet Canadian Building Code Requirements


NOTICE: FIRE TESTING STANDARDS REQUIRE THE FIREWRAP TO BE INSTALLED CONTINUOUSLY ALONG THE DUCTWORK IN THE SAME MANNER AS A GYPSUM SHAFT INTERMITTENT INSTALLATION IS NOT ALLOWED.


- Rated for 229mm (9”) clearance from duct to combustibles using 1-layer of CL4FIRE Code-96™ Rated for 0mm clearance from outside of insulation to combustibles using 1-layer of CL4FIRE Red or CL4FIRE Code-96™ on the inside layer and 1-layer of CL4FIRE Code-96™ on the exterior layer for a total of 76mm (3”) thickness overall.

- Exterior steel chicken wire mesh installed beneath CL4FIRE Code-96™ jacketing. It is a mandated requirement and outlined by the Canadian Construction Materials Centre (CCMC) and is the only product allowed to meet protection, integrity, and movement criteria of NFPA-96 for both normal building temperatures and hot fire exposures.


Single 38mm (1 1⁄2”) thick layer installation of CL4FIRE Code-96™ wrap allows for minimum 23cm (9”) clearance from ductwork to combustibles. 76mm (3”) overlaps at all single layer installation joints installed as outlined in QAI listed system F-401-1-1 for up to a 2-hour fire rating.


CL4FIRE Double Layer Grease Duct System

Listed System: F405-1-4


Traditional Double Layer Grease Duct System


- Same great installation features as the Single Layer System but requiring 2-layers of CL4FIRE insulation.